PLANT EQUIPMENTS LONG SHUTDOWN PRESERVATION METHODS | ||
SL NO. | EQUIPMENT | PRESERVATION METHOD |
A | MECHANICAL | |
1 | Boiler | 1-Wet preservation (If shutdown period is up to one month) Maintain pH: 10-10.5 Hydrazine concentration :> 200 ppm Note: Check water sample at various locations like steam drum, mud drum, super heater, economiser & Water wall tubes. Concentration should be same at all collection points 2-Dry Preservation (If shutdown period is more than one month) |
2 | Deaerator & Surge tanks | Wet preservation Maintain pH: 10-10.5 Hydrazine concentration :>200 ppm |
3 | Travelling grate (TG) | After cleaning, inspection & Maintenance, keep run TG at least 10-15 minutes on every 6-7 days to avoid shaft jam in bush/bearings |
4 | ESP | After cleaning & Inspection, close all the man hole doors air tight & keep lime trays at various locations to avoid moisture accumulation on internals |
5 | APH & Economiser | After cleaning & Inspection, close all man hole doors air tight & keep lime trays at various locations to avoid moisture accumulation on internals |
6 | Boiler fans | After cleaning & Inspection..close all man hole doors air tight Change the shaft orientation at every 10-15 days by rotating shaft manually to avoid shaft sagging/bending |
7 | Boiler feed pumps | Keep suction valve open Change the shaft orientation at every 10-15 days by rotating shaft manually to avoid shaft sagging/bending |
8 | Air Compressors | Operate Air compressors at least 10-15 minutes at every 7-8 days or else rotate the flywheel one complete rotation |
9 | Main & Auxiliary cooling water pump | Rotate the shaft on every 10-15 days to avoid impeller jam in wear ring |
10 | Steam Turbine | 1-Turbine dehumidification by blowing hot air through Turbine HP suction to LP suction & ensure relative humidity in Turbine is <40% 2-Put turbine on barring gear for 20-30 minutes at every 6-7 days 3-Operate HP & LP valves from 0 to 100% at every 15 days 4-Operate ESV at every 15 days |
11 | Turbine lub oil system | Keep "ON" oil centrifuge at least twice in a week |
12 | Ash handling system | Ensure all ash handling & storage systems are clean to avoid rusting/corrosion |
13 | Fuel feeding system | Maintain fuel feeding system internals clean to avoid corrosion & rusting |
B | E&I | |
1 | Generator | Keep "ON" Generator space heaters for 8-10 hours if atmosphere temperature is very less (In rain & winter seasons) |
2 | Power Transformer | Charge transformers at least 6-8 hours at every week to avoid moisture formation in oil |
3 | VFD drives | Keep charged all VFD drives continuously Note: Avoid interruption of power supply to VFDs |
4 | Batteries | Inspect battery voltages regularly (twice in a month) |
5 | UPS & AVR | Check Healthiness of redundancy systems regularly |
6 | Motors | 1-Cover all motors terminals by polythene covers to avoid entry of rain water 2-For higher KW motor keep "ON" space heaters |
7 | MCC & PCC | Keep lime trays at MCC, PCC to avoid moisture formation |
8 | DCS | Ensure DCS healthiness regularly Note: If DCS kept OFF, inspect the panels regularly to ensure rats/lizards are not entering into the panels |
C | WTP | |
1 | RO plant | Preserve RO membranes with 2-3% SMBS or other chemical for 30-40 days. After that drain the preserved water & perform membrane flushing on every 7-8 days |
2 | Cooling tower | If CT is not necessary in shutdown, drain the cooling tower ,clean the sumps & apply lime |
3 | Cat ion & Anion Resin | Maintain normal water level in vessels Replace the vessels water at every 10-15 days |
D | SAFETY | |
1 | Fuel yard & Fuel handling | Depute a particular person to have daily round to avoid fire incidents due to saturation of coal/bagasse or any other fuel |
2 | Fire fighting system | Conduct fire fighting pumps trial (especially Diesel fire fighter pump & Main fire fighter pump) to ensure healthiness |
3 | Plant fire alarm system | Check Healthiness of fire alarm systems regularly |